By collecting data on currents, L411 loggers help to identify potential problems before they become critical (e.g. overheating, overloading, etc.). Recording can also provide evidence of an outage or variation that has caused a malfunction.
Loggers can be used to monitor and analyse energy consumption in buildings or on an industrial load, in order to optimise energy efficiency.
These L411 current loggers operate over very long periods if required, and are very simple to set up. The devices can communicate via their USB port, but can also be networked via their WiFi mode. The Data Logger Transfer software is used to configure the devices and process all the measurements.
• 1 measurement channel
• Measurements from 0.5 to 3000 A AC
• Backlit LCD display
• 8 GB memory size
• Acquisition speed of 1 measurement / s
• Aggregation from 1 to 60 min
• Communication via USB, Wifi, Web server and IRD server DataView Synch
• Powered by 3 AA batteries or USB
• Battery life is 3 days recording without Wi-Fi
• Optional shock-proof casing
• Dimensions 147 x 34 x 72 mm
• Weighs approximately 300 g
• Current sensor Ø 100mm and length 350mm
• 1.2 m current sensor lead
• Operating temperature from -20°C to 50°C
• Protection class IP54
• Electrical safety IEC 61010 600 V CAT IV / 1000 V CAT III