New T82N analog measurement transducer for reactive power compliant with the requirements of the latest product standards
Product for the severest environments such as the nuclear sector
Model: QAR 1232B
Type of measurement: reactive power
Transfer curves: linear
Rated Ph - Ph voltage: direct from 100V to 400Vac 50/60Hz
Rated Ph - N voltage: direct from 100V/√3 to 400V/√3 50/60Hz
Rated current In: direct, 1 or 5A
Measurement range: 0...1,3 Un
Auxiliary source: 100/√3 to 440Vac 50/60Hz and 24 to 125Vdc
Current output: 0 to 20mA
Voltage output: 0 to 10V
Accuracy class: 0.5%
Response time: 260 ms
Insulation: 2 kV
Ingress protection: IP20
Operating temperature: -10°C to +60°C
Type of mounting: plate-mounted or on socket
Reference standard: EN 60688 of April 2013
Related products:
Socket for screw-on front connector, reference: EMBB4005
Symmetrical DIN rail adapter, reference: PDINSYME
Asymmetrical DIN rail adapter, reference: PDINASYM